Dynamic Analysis of Multistory Building With and Without Shear Wall and Bracing System

  • Unique Paper ID: 161195
  • Volume: 10
  • Issue: 2
  • PageNo: 922-926
  • Abstract:
  • Rapid growth of urban population and lack of availability of land tends to produce shortage of land and high cost of land hence to overcome these crises high rise structures are preferred. Along with vertical loads such as self weight of structure, live load; structure has to resist the horizontal loads such as seismic load and wind load. There are different types of lateral load resisting systems such as shear wall, outrigger, bracing, hexagrid, diagrid, rigid frame, etc. According to site condition, types of building these systems are used. In this study Shear wall system and Bracing systems are used for 25 stories multistory building different types of shear wall and bracing systems are used for analysis. The analysis of building is done by linear dynamic method i.e. response spectrum method

Cite This Article

  • ISSN: 2349-6002
  • Volume: 10
  • Issue: 2
  • PageNo: 922-926

Dynamic Analysis of Multistory Building With and Without Shear Wall and Bracing System